BACnet Insight
7.9. Virtual 1 Required to be present in any one protocol level.
This table is valid for devices that claim PR 18 or greater. 2 Required to be present if PR >= 18 and <= 23.
Diese Tabelle gilt für Geräte, die PR 18 oder höher beanspruchen.
A proprietary NPO represents a non-BACnet network supported by a device. The topmost
Property Identifier Protocol_Level Conformance
Protocol_Level must be NON_BACNET_APPLICATION.
Network_Number BACNET_ R, W 1 A proprietary NPO presents a non-BACnet network as an object that contains properties
APPLICATION
that can be read or written using BACnet services. This NPO cannot represent a BACnet
Network_Number_Quality BACNET_ R network and cannot be part of a BACnet internetwork.
APPLICATION
APDU_Length BACNET_ R NOTE: Any standard NPO property may be present in the object. If the presence or
APPLICATION capability of one of these properties requires other properties to be present, then the
MAC_Address R 2 other properties must also be present.
Link_Speed PHYSICAL O 3 1 Muss in einer beliebigen Protokollebene vorhanden sein.
1 Required to be writable. 2 Muss vorhanden sein, wenn PR >= 18 und <= 23.
2 Required to be present in any one protocol level.
Ein proprietäres NPO repräsentiert ein Nicht-BACnet-Netzwerk, das von einem Gerät
3 Required to be present if PR >= 18 and <= 23.
unterstützt wird. Die oberste Protokollebene muss NON_BACNET_APPLICATION sein.
A Virtual NPO represents a non-BACnet network of non-BACnet devices as a virtual
BACnet network. Ein proprietäres NPO stellt ein Nicht-BACnet-Netzwerk als Objekt dar, das Eigen-
schaften enthält, die mit BACnet-Diensten gelesen oder geschrieben werden können.
NOTE: The device is a BACnet router between one or more BACnet networks and one or Dieses NPO kann kein BACnet-Netzwerk darstellen und kann nicht Teil eines BACnet-
more virtual BACnet network. See 135-2024, Clauses H.1.1.1 and H.1.1.2.# Internetwerks sein.
1 Muss beschreibbar sein.
2 Muss in einer Protokollebene vorhanden sein. HINWEIS: Jede Standard-NPO-Eigenschaft kann im Objekt vorhanden sein. Wenn
3 Muss vorhanden sein, wenn PR >= 18 und <= 23. das Vorhandensein oder die Fähigkeit einer dieser Eigenschaften das Vorhandensein
anderer Eigenschaften erfordert, müssen auch die anderen Eigenschaften vorhanden
Ein virtuelles NPO stellt ein Nicht-BACnet-Netzwerk von Nicht-BACnet-Geräten als vir- sein.
tuelles BACnet-Netzwerk dar.
HINWEIS: Das Gerät ist ein BACnet-Router zwischen einem oder mehreren BACnet-
Netzwerken und einem oder mehreren virtuellen BACnet-Netzwerken. Siehe 135-2024, ABOUT THE AUTHOR
Abschnitte H.1.1.1 und H.1.1.2.
Michael Osborne has over 35 years’ experience in various aspects of the high-tech
7.10. ZigBee industry. For the last 19 years, Michael has designed building automation products,
This table is valid for devices that claim PR 18 or greater. managed technical projects, and supervised a team of talented developers. For most
Diese Tabelle gilt für Geräte, die PR 18 oder höher beanspruchen. of his time in the building automation industry, Michael has also been involved in
the BACnet community where he developed tests for the ASHRAE 135.1 Testing
Property Identifier Protocol_Level Conformance
Standard and wrote proposals for the ASHRAE SSPC 135 Standard. From 2012 to
Network_Number BACNET_APPLICATION R, W 1
2021, Michael was the Secretary, Vice-Chair and finally Chair of the ASHRAE SSPC
Network_Number_Quality BACNET_APPLICATION R 135 Committee.
APDU_Length BACNET_APPLICATION R
MAC_Address PHYSICAL R ÜBER DEN AUTOR
Link_Speed PHYSICAL O 2
Michael Osborne has over 35 years’ experience in various aspects of the high-tech
1 Required to be writable if a device is a BACnet Router.
industry. For the last 19 years, Michael has designed building automation products,
2 Required to be present if PR >= 18 and <= 23. managed technical projects, and supervised a team of talented developers. For most
1 Muss beschreibbar sein, wenn es sich bei einem Gerät um einen BACnet-Router
handelt. of his time in the building automation industry, Michael has also been involved in the
BACnet community where he developed tests for the ASHRAE 135.1 Testing Standard
2 Muss vorhanden sein, wenn PR >= 18 und <= 23.
and wrote proposals for the ASHRAE SSPC 135 Standard. From 2012 to 2021, Michael
7.11. Proprietary was the Secretary, Vice-Chair and finally Chair of the ASHRAE SSPC 135 Committee.
This table is valid for devices that claim PR 18 or greater.
Diese Tabelle gilt für Geräte, die PR 18 oder höher beanspruchen.
Property Identifier Protocol_Level Conformance
Network_Number BACNET_APPLICATION R
Network_Number_Quality BACNET_APPLICATION R
Michael Osborne
APDU_Length BACNET_APPLICATION R
BTL Technical AdvisorBACnet International
MAC_Address R 1 mike@bacnetinternational.org
Link_Speed PHYSICAL O 2 www.bacnetinternational.org