          Technical Monitoring – The Foundation for

          Energy Efficiency, Decarbonisation and


          Digitalisation


          Technisches Monitoring – Fundament für


          Energieeffizienz, Dekarbonisierung und


          Digitalisierung





          For  decades, building automation has been  potentials  of  more  than  20%  lie  dormant  in  are appropriately engineered. Where Modbus
          attributed with significant potential for energy  almost all building portfolios.  or KNX systems are used, structured data point
          savings. In practice, however, these promises have                   lists must be provided. A decisive factor for
          largely remained unfulfilled across the building  Technical Monitoring Instead of Blind AI   efficient implementation is the standardisation
          stock. The cause is not a lack of technology,  Enthusiasm            of data point naming, for example through
          but rather its incorrect or insufficient use during                  the BACtwin User Addressing System (BAS)
          operation.                        A growing PropTech industry promises exactly  in accordance with AMEV Recommendation
          Seit Jahrzehnten wird der Gebäudeautoma-  these savings – often under the label of “artificial  174. Open platforms such as the B-CON
          tion ein erhebliches Energieeinsparpotenzial  intelligence”. This usually requires connecting  suite  enable  coordination-free integration  of
          zugeschrieben. In der Praxis bleiben diese   building services systems to cloud-based  technical monitoring by translating data into the
          Versprechen jedoch in der Breite unerfüllt.   services. However, the principle applies: “Shit  BACtwin BAS – both for integrated, on-premises
          Ursache ist nicht ein Mangel an Technik,   in, shit out.” As long as systems are incorrectly  technical monitoring within the management and
          sondern deren fehlerhafte oder unzurei-  configured or defective, AI cannot deliver  operating system and for the optional connection
          chende Nutzung im Betrieb.        sustainable optimisation. In addition, particularly  of external solutions, such as those offered by
                                            in critical infrastructure (KRITIS) environments,  TÜV Süd or other providers.
          Particularly in non-residential buildings, it  external internet connections are viewed critically
          becomes evident that existing automation  from an IT/OT security perspective. On-premises  From Monitoring to Optimisation
          systems fail to realise their potential without  solutions operated within the building owner’s IT
          continuous monitoring and professional technical  infrastructure are significantly more robust and  Once technical monitoring has been imple-
          management.                       secure.                            mented, responsibility lies with the building
                                                                               operator to remedy the identified faults. This
          Regulatory Pressure from EPBD 2024  Technical Monitoring as the Basis  requires in-depth understanding of the build-
                                                                               ing services systems, which is often not avail-
          Against this background, legislators have taken  Through systematic and recurring supervision,  able on site. Coordination is therefore ideally
          action. With the revised European Performance  technical monitoring ensures that malfunctions  carried out by specialised internal departments
          of Buildings Directive (EPBD 2024), technical  and misconfigurations are detected and  or external engineering service providers. Only
          commissioning  management  for  new  non-  reported. It is essential for proper acceptance  once  proper  operation has been  ensured do
          residential  buildings  with  a  thermal  rated  in accordance with AMEV Recommendation  further optimisation measures unfold their full
          output above 290 kW – and above 70 kW from  170, for subsequent energy-efficient operation,  potential – for example predictive operating
          2030 onwards – has become mandatory. The  and for overall operational reliability. Experience  strategies that take weather forecasts or occu-
          objective is to ensure the energy performance of  shows that achieving average savings of around  pancy  predictions into  account, regardless of
          building services systems from the outset and to  20% – and in individual cases up to 40–50%  whether these approaches are primarily based
          maintain it over the long term.   – typically does not require major investments,  on thermal building models or on data-driven
                                            but rather transparency regarding the actual  AI methods.
          Main Causes of Energy Waste       system condition combined with sound expertise
                                            in building services engineering.  Standards and Guidelines as a Framework
          The greatest energy losses occur in heating,
          ventilation and air-conditioning (HVAC) systems.  Open Data Platforms and Standards  The technical foundation for technical monitor-
          Frequently, systems  are operated  in manual                         ing is provided, among others, by the following
          mode, with incorrect setpoints or unsuitable  BACnet-based systems demonstrate one of their  standards and guidelines:
                                                                                 A
          time schedules, or were never properly  key strengths in this context. They generally  ƒ  MEV Recommendation 158 – Technical
          commissioned. Without systematic monitoring,  allow technical monitoring to be retrofitted with   Monitoring
                                                                                 A
          such faulty conditions often remain undetected  relative ease, as data points can be read directly  ƒ  MEV Recommendation 170 – Commission-
          for years. As a result, energy and CO  reduction  from the network – provided that the controllers   ing Management
                                   2