Page 18 - 240909_BACnet_Europe-Journal_41
P. 18

BACnet Insight



                                                                               The table on p. 23 below shows an overview of the
                                                                               requirements. A tick stands for legally unambiguous
                                                                               requirements. A question mark is shown where there is
                                                                               room for legal interpretation. Where there is a horizon-
                                                                               tal bar, there are no legal requirements based on § 71a.

                                                                               Existing Non-Residential Buildings

                                                                               If the nominal output of the heating/air conditioning sys-
                                                                               tem in an existing building does not exceed 290 kW, no
                                                                               legal requirements based on § 71a must be observed.

                                                                               If this threshold value is exceeded, energy monitoring
          Mit dem GEG 2024 wurde für Nichtwohngebäude erstmals ein Mindest-Automatisierungsgrad eingeführt.
          The German GEG 2024 introduced a minimum level of automation for non-residential buildings for the first time.  technology including data exchange via company and
                                                                               manufacturer-independent interfaces must be guar-
                                                                               anteed in any case. It is unclear whether the “automa-
          Heating                           directly support a standardized communication protocol   tion level B or better” must then also be implemented.
          ƒ  Automated room temperature control with   or be converted to standardized communication proto-  According to the BMWK’s statement, this is not neces-
           communication (e.g. time programs, flow temperature   cols via gateways or corresponding controllers.  sary and if this level of automation is not introduced out
           adaptation)                                                         of own motivation (reduction of operating costs), it is
          ƒ  Heat transfer for hall heating systems: Time program   The issue of defining the central communication proto-  advisable to make a note in the file with reference to this
           with optimized on/off switching  col is therefore of particular importance. The difference   BMWK statement. However, if a major renovation of the
          ƒ  Demand-driven flow temperature control  between interfaces and the actual communication proto-  heating or cooling system is to be carried out in an exist-
          ƒ  Regulation or control of the circulation pumps:   cols should be emphasized here. Interfaces include, for   ing BMS – e.g. replacing an oil boiler with a heat pump
           Differential pressure control    example, Ethernet or RS 485; however, these are quite   – the planner should also explicitly agree with the client
          ƒ  Heat generation: Weather-compensated control   universally applicable and the definition of one or the   the extent to which the degree of automation should be
           including room temperature activation  other is not sufficient! It is not only important to spec-  taken into account.
                                            ify that systems and applications can transfer data, but
          Cooling                           also that the content of the data is interpreted correctly.   New non-residential buildings
          ƒ  Cold transfer (intermittent operation): Time program   Protocols such as Modbus, OPC UA, MQTT or BACnet
           with optimized on/off switching  should be mentioned here. BACnet has the advantage of   If the nominal output of the heating/air conditioning sys-
          ƒ  Partial interlock between heating and cooling  a consistent focus on the requirements of building auto-  tem in a new building exceeds 290 kW, automation level
          ƒ  Demand-driven flow temperature control  mation with different interface support (e.g. as BACnet   B and cross-system and cross-manufacturer communi-
          ƒ  Regulation or control of the circulation pumps: Differ-  MS/TP, BACnet/IP or BACnet/SC).  cation between all technical building systems and appli-
           ential pressure control                                             cations must be clearly guaranteed.
          ƒ  Cooling generation: Demand-driven control   Requirements According to GEG 2024
                                                                               If the value falls below this threshold, the question arises
          AHU/air conditioning              The legal requirements are listed in the GEG in § 71a.   as to whether the listed requirements also apply. Accord-
          ƒ  Presence-dependent air volume flow control  Unfortunately, there are different legal interpretations of   ing to the BMWK, this should not be the case, but as
          ƒ  Cooling load-dependent variable volume flow and   the wording.    before, this is not legally binding and could be decided
           demand-controlled temperature with communication                    differently in court. It is therefore advisable to make a
                                            The BMWK (Federal Ministry for Economic Affairs and   note in the file and provide an exact description or exclu-
          Lighting/Shading                  Climate Protection) has published a statement on the   sion of the automation requirements between the client
          ƒ  Daylight-dependent dimmed lighting (switches off,   legally ambiguous requirements, which unfortunately   and the planner.
           switches on again automatically) with presence detector  begins with the note that this is not a legally binding
          ƒ  Automatically operated sun and glare protection with   statement and may be decided differently in court. This   Comprehensive White Paper on the Topic
           slat tracking                    means that a certain amount of uncertainty will remain
                                            until the first court rulings are made, but this should be   Further information and the exact wording of the BMWK
          Technical Facility Management     kept under control by taking appropriate notes or clarify-  (Federal Ministry of Economics and Climate Protection)
          ƒ  Central adaptation of user requirements  ing matters with clients.   statement are available in a free White Paper – download
                                                                               at www.big-eu.org/resources.
          Data Communication

          In addition, the GEG 2024 requires communication
          between the technical building systems and the appli-
          cations, even with different proprietary technologies;   Prof. Dr. Michael Krödel
          for this purpose, the integrated components must either
                                                              Professor für Gebäudeautomation und -technologie
                                                              bei der Technischen Hochschule Rosenheim
                                                              michael.kroedel@th-rosenheim.dewww.th-rosenheim.de



          18  BACnet Europe Journal 41 09/24
   13   14   15   16   17   18   19   20   21   22   23